Baldor ID101F50-E Yard Vacuum User Manual


 
3-12
Operation
71-Analog Output Select - Allows setting of the analog output
available at the control terminal MET to represent various drive
operating conditions. The analog output is 0 to 10 VDC nominal.
The analog output is useful in applications where a higher level
control is monitoring the operation of the control to make process
decisions based on the current status of the inverter. The output
can also be used to drive remote analog meters that may be
located near the operator. Please review the Analog Output
Table below for the available operating condition selections.
Parameter 71-ANALOG OUTPUT SELECT
Value Description
0
Output Of
f
1
Output Frequency
, Full scale = Parameter 32- MAXIMUM
OUTPUT FREQUENCY
2
Output Current, Full Scale = 200% of Rated Current
3
Drive Load, Full Scale = 200% of Rated Load
75-Relay Output Select - Allows setting of the normally open
and normally closed relay outputs available at the control
terminal strip to represent various drive operating conditions.
The relay outputs are useful in applications where a higher level
control is monitoring the operation of the control to make process
decisions based on the current status of the inverter. These
outputs can also be used to interlock into mechanical brakes,
bypass contactors, and signal an operator if various operating
conditions are present. Please refer to the Relay Output Select
Table for the available operating condition selections.