Baldor ID101F50-E Yard Vacuum User Manual


 
3-14
Operation
occurrence. The elapsed time is indicated in 0.1 hour
increments with 0.9 hour maximum displayed. The two left most
digits displayed is the fault code and the right most digits is the
elapsed time.
24-Analog Command Select - Selects the type of external
speed reference command the control should be expecting to
see in your application. The possible values are 0-10V, 0-5V,
0-20mA, and 4- 20mA. If long distances are required between
the control and the external speed command location then 0-20
mA or 4-20mA should be considered since a current loop
command scheme will allow no loss of the command signal with
long cable lengths.
Also sets if the control will recognize a high value of command
signal as a high output command or a low output command of
the inverter. If Direct is selected the control will see a low
command signal as a low speed command and a high command
signal as a high speed command. Direct is the selection used in
most applications. If Inverted is selected the control will see a
low command signal as a high speed command and a high
command signal as a low speed command.
Parameter 24-ANALOG COMMAND SELECT
Value Operation
Analog Command Signal
0 Direct
0-10 VDC, 0-5 VDC, 0-20 mA
1 Inverted
10-0 VDC, 5-0 VDC, 20-0 mA
2 Direct
4-20 mA
3 Inverted
20-4 mA
33-Preset Speed #1 - Sets the output frequency when Preset
Speed #1 is commanded at the Control Terminal Strip. The
adjustable range is 0.1-400 Hz. The factory setting is 5 Hz.
34-Preset Speed #2 - Sets the output frequency when Preset
Speed #2 is commanded at the Control Terminal Strip. The
adjustable range is 0.1-400 Hz. The factory setting is 20 Hz.