62-Load Torque Limit REV - Sets the maximum amount of
current that is supplied to the motor under a motoring reverse
condition before Torque Limiting takes affect. The range of
adjustment is 30- 150% of parameter 03-Rated Current. The
factory setting is 150%.
63-Regen Torque Limit FWD - Sets the maximum amount of
current that is absorbed by the control from the motor under a
regenerative forward condition before Torque Limiting takes
affect. The range of adjustment is 30-110% of parameter
03-Rated Current. The factory setting is 80%.
64-Regen Torque Limit REV - Sets the maximum amount of
current that is absorbed by the control from the motor under a
regenerative reverse condition before Torque Limiting takes
affect. The range of adjustment is 30-110% of parameter
03-Rated Current. The factory setting is 80%.
68-Number of Restarts - Sets the maximum number of
automatic restart attempts that is allowed before the control will
require a manual restart. After ten minutes without reaching the
maximum number of faults, the number of allowable restarts will
be reset to the value specified in the Number Of Restarts
parameter. This feature is useful in applications that require
unattended operation and automatic operation even in the event
of various fault conditions such as unscheduled power outages.
The control will not automatically clear faults F01 through F10.
The adjustable range is 0 - 8. the factory setting is 0 effectively
disabling the Auto Restart function.
69-Restart Delay - Sets the amount of time allowed between a
fault condition (F11 through F20) and an automatic restart. This
feature is useful in setting a sufficient time period for a fault
condition to be cleared before an automatic restart is attempted.
The adjustable range is 0 to 60 seconds.