AOC 15 Portable Generator User Manual


 
9.0 Wind Turbine Operation
NOTICE: Use of the material contained in this document is subject to the warning on page Iv and the disclaimer
on page v of this document.
DOC012R02 AOC 15/50 User Manual Nov 2001
70
The PLC monitors the system parameters continuously as shown in Table 9.1-2. When a system
parameter is out of range or a fault has been registered, the PLC takes appropriate action by
disconnecting and either parking or freewheeling the wind turbine. Following this, it will
continue to monitor the parameters and faults, resetting the system once they have cleared.
Rotor over-speed faults and parking brake undercurrent faults require to be reset manually. The
turbine TEST/OFF/ON switch must be switched to OFF first and then back to ON; it is the
change from OFF to ON that resets the faults. All other faults reset automatically once the
cause of the fault has cleared. An optional low power fault is included in some controllers to
shut down the wind turbine, should the output drop significantly below the values expected at a
given wind speed. This fault resets automatically, unless it has occurred three times within 75
minutes, in which case a manual reset is required.
During any fault related shutdown, the tip and dynamic brakes activate immediately, with the
dynamic brake providing a large portion of the braking torque. Application of the parking brake
is normally delayed until the rotor has slowed down sufficiently using the tip and the dynamic
brakes. During a loss of utility power to the controller, all brakes are applied simultaneously.
Thirty three percent of the dynamic brake capacitance is disabled to allow an immediate torque
contribution by the parking brake, keeping the overall braking torque within safe limits.
Turbine TEST:
When set to TEST the parking brake, dynamic brake and rotor jog switches can be energized.
9.1.2 Heater ON
The generator winding and the parking brake heaters prevent condensation from collecting on
the windings and the parking brake, respectively. They can be activated manually at the
operator's discretion when the dew point is high but only when the wind turbine is disconnected
from the grid. When the main contactor is closed, the PLC automatically de-energizes the
heater circuit. An optional transmission heater can be provided for severe cold weather sites.
9.1.3 Parking Brake Release
The parking brake release switch allows the operator to release the parking brake when the wind
turbine is in test mode and no grid faults, over-speed or high winds have been registered. It is
not necessary to release the brake manually during normal operation.