Xantrex Technology PV225S-480-P Portable Generator User Manual


 
Operation
2–18 152607
Time Delay for PV
Wake up
Displays as:
PV T Start:
Time delay to transition from PV
wake up state to PV On-line state.
Once the inverter is in PV Wake
Up mode, it waits for the amount
of time determine by this
parameter before transitioning into
PV on-line mode. During this time
the inverter checks that the PV
voltage is no less than the PV
wake voltage, otherwise it goes
into PV Sleep mode.
39 Seconds 300 1200 0
Time delay for PV
Sleep Test
Displays as:
PV T Stop:
This is the amount of time the
inverter will be in Sleep Test mode
if the output power continues to be
below “PV P Stop”. The inverter
will exit Sleep Test mode towards
on-line mode if the power is over
“PV P Stop” or towards Shutdown
mode if the “PV T Stop” timer
expires.
40 Seconds 300 1200 0
PV Output Power to
Enter Sleep Test
Mode
Displays as:
PV P Stop:
This is the output power trigger
point for the inverter to transition
into sleep test mode. When the
output power is below the value of
this parameter the inverter enters
sleep test mode.
41 KW 1 10.0 0.1
Power Tracker
Maximum Output
Power
Displays as:
I PPT Max:
This parameter sets the percentage
of maximum rated power the
inverter will produce when in
power tracker mode. For example,
a 100 Kw system with this
parameter set to 50 will not
attempt to produce more than 50
Kw.
42 Percentage
of
maximum
output
power.
100 110 0
Manual Current
Output
Displays as:
I Manual:
This parameter sets the percentage
of maximum out current the
inverter will attempt to produce
while in manual current mode.
43 Percentage
of
maximum
output
current.
25 110 0
Table 2-5
Write Menu Parameters
Parameter Description ID Units
Default
Value
Maximum
Value
Minimum
Value