6.4 Analog signals for frequency setting
6.4.1 Setting frequency command characteristics
H : Analog input/logic input function selection
H : VI/S3 reference point 1 setting (%)
H : VI/S3 reference point 2 setting (%)
H : V1/S3 point 1 frequency (Hz)
H : V1/S3 point 2 frequency (Hz)
Function
By changing the setting of
H
, the function of the VI/S3 terminal can be switched
between 0~(5)10Vdc voltage input and 4~20mAdc current input.
The
H
to
H
parameters are used to adjust the output frequency according to the
analog signal (voltage: 0~(5)10Vdc, current: 4~20mAdc) from an external device.
Parameter setting
Title FunctionAdjustment range Default setting
H
Analog input/logic input
function selection
0: Voltage signal input (0~10(5)Vdc)
1: Current signal input (0(4)~20Adc)
2: Contact input
0
H
VI/S3 reference point 1
setting (%)
0100(%) 0
H VI/S3 point 1 frequency (Hz)
0.0200.0(Hz)
0.0
H
VI/S3 reference point 2
setting (%)
0100(%) 100
H
VI/S3 point 2 frequency (Hz)
0.0200.0(Hz)
*
Note 1:Do not specify the same value for input points 1 and 2. If you do so, the error message
GTT” will be displayed.
*The value is changed according to the set-up parameter condition.
(VFNC1 (S)-□□□□P-W type)
80 [Hz] for VFNC1 (S)-□□□□P type.
F (F: Forward run)
CC
S2(THR2)
R(AD2)
S1(MCHG)
Forward run command
Switching to motor 2
Switching to acceleration/deceleration 2
Switching to thermal 2