Table of output terminal functions 1
Function
No.
Code Function Action
0LL Frequency lower limit
ON :Output frequency higher than NN setting
OFF: Output frequency equal to or lower than NN
setting
1LLN Inversion of frequenc
y
lower limit Inverse output of LL
2UL Frequency upper limit
ON :Output frequency equal to or higher than WN
setting
OFF: Output frequency lower than WN setting
3ULNInversion of frequenc
y
upper limit Inverse output of UL
4LOW
Low-speed detection signal
ON :Output frequency equal to or higher than
H setting
OFF: Output frequency lower than H setting
5LOWN
Inversion of low-speed detection
signal
Inverse output of LOW
6 RCH
Designated frequency reach
signal (completion of
acceleration/deceleration)
ON :Output frequency within command frequency
±2.5Hz
OFF: Output frequency exceeding command
frequency ±2.5Hz
7 RCHN
Inversion of designated
frequenc
y
reach si
g
nal
(
inversion
of completion of
acceleration/deceleration)
Inverse output of RCH
8 RCHF Set frequency reach signal
ON :Output frequenc
y
within H settin
g
±2.5Hz
OFF: Output frequency exceeding H setting
±2.5Hz
9 RCHFN
Inversion of set frequency reach
signal
Inverse output of RCHF
10 FL Failure FL (trip output) ON :Inverter trips
11 FLN
Inversion of failure FL (inversion
of trip output)
Inverse output of FL
12 OT Over-torque detection
ON :Torque current is held above the torque set with
H for a period of time lon
g
er than that set
with H.
13 OTN
Inversion of over-torque
detection
Inverse output of OT