Baldor GLC20 Portable Generator User Manual


 
4‐32 Operation MN2408
Figure 4‐18 Analog Fault Menu Loop Parameters
Fault Name Input Analog
Type
Fault
E=Enable
D=Disable
Setpoint Level
(Pick-up)
Setpoint Level
(Drop-out)
Action
S=Shutdown
A=Alarm
Alarm Latch
Y=Yes
N=No
Bypass On
Start
Y=Yes
N=No
Transient
Delay (Sec)
Under Voltage AC Voltage E* S Y Y* 5.0
Under Frequency AC Frequency E* S Y Y* 5.0
Weak Battery DC Voltage E* 18.0 N/A A* Y N* 3.0
Low Battery
Voltage
DC Voltage E* 25.6 N/A A* N N* 120.0
High Battery
Voltage
DC Voltage E* 30.4 N/A A* N N* 10.0
Low Engine Temp Temp Sender E* 95 F N/A A* Y N* 5.0
High ENG Temp #1
Alarm
Temp Sender E* 198 F N/A A Y Y 2.0
High ENG Temp #2
Shutdown
Temp Sender E* 206 F N/A S Y Y 2.0
Low Oil Press #1
Alarm
Press Sender E* 30PSI N/A A Y Y* 2.0
Low Oil Press #2
Shutdown
Press Sender E* 20PSI N/A S Y Y* 2.0
* Indicates parameter is non-programmable.
Figure 4‐19 Digital Fault Menu Loop Parameters
Fault Name Input # Action
S=Shutdown
A=Alarm
Alarm Latch
Y=Yes
N=No
Polarity
O=Open
C=Close
Bypass On
Start
Y=Yes
N=No
Transient
Delay (Sec)
Low Oil Pressure 1 S - O Y 0.5
High ENG TEMP 2 S - O Y 1.0
Batt Chgr Input Fail 3 A Y C N 30.0
Low Fuel Level 4 A N C N 0.1
Figure 4‐20 Calibration Menu Loop Parameters
Parameter Setting
Volts A-B Zero XXX XXXVAC
Volts A-B Span XXX XXXVAC
Volts B-C Zero XXX XXXVAC
Volts B-C Span XXX XXXVAC
Volts C-A Zero XXX XXXVAC
Volts C-A Span XXX XXXVAC
Volts A-N Zero XXX XXXVAC
Volts A-N Zero XXX XXXVAC
Volts B-N Zero XXX XXXVAC
Volts B-N Zero XXX XXXVAC
Volts C-N Zero XXX XXXVAC
Volts C-N Zero XXX XXXVAC
Current A Zero XXX XXXAAC
Current A Span XXX XXXAAC
Current B Zero XXX XXXAAC
Current B Span XXX XXXAAC
Current C Zero XXX XXXAAC
Current C Span XXX XXXAAC
Battery Voltage Span XXX XX.X VDC
Engine Temperature XXX XXX C/F
Oil Pressure XXX XXXX PSI/KPA