4‐22 Operation MN2408
Timer Countdown Timer countdown menus are automatically displayed when a specific time delay function
occurs during a control sequence. When a time delay begins, the LCD display will show the time
delay function name (i.e. Engine Start Delay) and the current time remaining in the countdown
sequence. When the timing function has expired, the LCD display will automatically change to
either the next timing sequence countdown display or return to the original system status menu.
Action
Description Display Comments
Apply Power and
Reset faults.
Main LCD Display.
Vavg
000
Aavg
000
Freq
000
Show Operating Status screens
ENGINE START
DELAY 45 SEC
Displays specific time delay function
name and remaining time.
Other time delay functions are:
ENGINE START
DELAY 45 SEC
CRANK PERIOD
XX SEC
REST PERIOD
XX SEC
STARTER RE-ENGAGE
DELAY XX SEC
BYPASS
DELAY XX SEC
COOLDOWN
DELAY XXXX SEC
WARMUP
DELAY XX SEC
RETURN
DELAY XX SEC
NEUTRAL
DELAY XX SEC
Note: Countdown screens only appear if Utility/Gen Ready To Load outputs are programmed.