Lincoln Electric SVM208-A Portable Generator User Manual


 
OUTPUT PROBLEMS
Observe Safety Guidelines detailed in the beginning of this manual.
PROBLEMS
(SYMPTOMS)
POSSIBLE AREAS OF
MISADJUSTMENT(S)
RECOMMENDED
COURSE OF ACTION
If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely,
contact the Lincoln Electric Service Department for technical troubleshooting assistance before you proceed.
Call 1-888-935-3877.
CAUTION
No auxiliary power - welding output
is normal - engine runs normally.
1. Check circuit breakers CB1 and
CB2. Reset if tripped.
2. Make sure that the control rheo-
stat (R1) is set at “GENERATOR”
(maximum).
3. Check for loose or faulty plug at
power receptacle.
1. Check the auxiliary power re -
ceptacles and associated wires
for loose or faulty connections.
2. Check the continuity (zero
ohms) of leads 3, 3A (black); 6,
6A (yellow); and 5 (white) from
the receptacles to the stator
windings. See the Wiring Dia -
gram.
3. Make sure lead 5 (white) is
grounded to the machine frame
(zero ohms).
4. Check for an open or grounded
auxiliary winding in the stator, 6
(yellow) to 3 (black). See the
Wiring Diagram.
TROUBLESHOOTING AND REPAIR
F-7 F-7
BULLDOG® 140
Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOC
Return to Master TOC Return to Master TOC Return to Master TOC Return to Master TOC