Fisher 444 Alphaline Weather Radio User Manual


 
Rosemount Model 444 Alphaline Temperature Transmitters
5-6
Centro Elettrotecnico Sperimentale Italiano (CESI/CENELEC) Certifications
E8 Flameproof:
EEx d IIC T6
I8 Intrinsic Safety:
Model 444RL
EEx ia IIC T6 (T
amb
= 40 °C) [P
i
= 0.75 W]
EEx ia IIC T5 (T
amb
= 55 °C) [P
i
= 1.0 W]
EEx ia IIC T4 (T
amb
= 80 °C) [P
i
= 1.0 W]
Model 444T_ & MV
EEx ib IIB T6 (T
amb
= 40 °C) [P
i
= 0.75 W]
EEx ib IIB T5 (T
amb
= 55 °C) [P
i
= 1.0 W]
EEx ib IIB T4 (T
amb
= 80 °C) [P
i
= 1.0 W]
Entity Parameters:
V
i
= 30 V dc
I
i
= 200 mA
P
i
= 0.75 W (T6)
P
i
= 1.0 W (T5)
P
i
= 1.0 W (T4)
C
i
= 0.024 F (Model 444RL)
C
i
= 0.006 F (Model 444T_ & MV)
L
i
= 0.
Special Conditions for Safe Use (“X”):
If the temperature sensor connected to the input circuit does not tolerate
an alternating tension of 500V for 60 seconds, the certified transducers
must be powered by galvanically-insulated equipment. Model 444RL
temperature transducers must be connected to associated electronic
equipment certified to EN 50.014/EN 50.020 standards.
British Approvals Service for Electrical Equipment Flammable Atmospheres
(BASEEFA) Type N Certification
N1 Ex N II T5
Maximum Voltage: 35 V dc
Maximum Current: 30 mA dc
An appropriate stainless steel tag will be supplied according to the certification
option selected.