Black Box Outlet Managed PDU Multi-tool User Manual


 
CHAPTER 13: Operation via SNMP
157
13.4.2. Plug Group Status/Control
ON, OFF, BOOT, and DEFAULT commands can be issued for plug groups via
SNMP. Plug groups are arranged in a table of 54 rows, one row for each plug group
in the system. Plug Group parameters are described below.
plugGroupTable::plugGroupName – String indicating the plug
groups name.
plugGroupTable::plugGroupAction – Action to be taken on
plug group
1 – Mark to turn ON (does not execute)
2 – Mark to turn OFF (does not execute)
3 – Mark to BOOT (does not execute)
4 – Mark to DEFAULT (does not execute)
5 – Mark to turn ON and execute plug group actions
6 – Mark to turn OFF and execute plug group actions
7 – Mark to BOOT and execute plug group actions
8 – Mark to DEFAULT and execute plug group actions
Set plugGroupTable::plugGroupAction to desired action, as specied
by values 1-4 above, for each plug group index the action is to be applied to. For
the last plug group you wish to set before executing the commands, use values 5-8
instead, which will invoke the requested commands all at once.
plugGroupTable::plugGroupCurrent – The current, in tenths of an
Amp, that is being consumed by each Plug Group.
plugGroupTable::plugGroupPower – The power, in Watts, that is
being consumed by each Plug Group.