13.3. Configuration via SNMP
Outlet Managed PDU User accounts can be viewed, created, modied, and deleted
via SNMP. User accounts are arranged in a table of 128 rows, and indexed 1-128.
User account parameters, as seen through the SNMP, are summarized below.
userTable::userName – 32 character username
userTable::userPassword – 16 character password
userTable::userAccessLevel – Account access level.
0 – View Access
1 – User Access
2 – Superuser Access
3 – Administrator Access
userTable::userLocalAccess – A string of 20 characters, with one
character for each of the 20 possible plugs on the LOCAL Outlet Managed
PDU. A ‘0’ indicates that the account does not have access to the plug, and a
‘1’ indicates that the user does have access to the plug.
userTable::userAux1Access – A string of 20 characters, with one
character for each of the 20 possible plugs on the AUX1 Outlet Managed
PDU. A ‘0’ indicates that the account does not have access to the plug, and a
‘1’ indicates that the user does have access to the plug.
userTable::userAux2Access – A string of 20 characters, with one
character for each of the 20 possible plugs on the AUX2 Outlet Managed
PDU. A ‘0’ indicates that the account does not have access to the plug, and a
‘1’ indicates that the user does have access to the plug.
userTable::userAux3Access – A string of 20 characters, with one
character for each of the 20 possible plugs on the AUX3 Outlet Managed
PDU. A ‘0’ indicates that the account does not have access to the plug, and a
‘1’ indicates that the user does have access to the plug.
userTable::userGroupAccess – A string of 54 characters, with
one character for each of the 54 possible plug groups in the system. A ‘0’
indicates that the account does not have access to the plug group, and a ‘1’
indicates that the user does have access to the plug group.
userTable::userSerialAccess – Access to the serial interface
0 – No access
1 – Access