Black Box Outlet Managed PDU Multi-tool User Manual


 
CHAPTER 1: Specifications
13
1. Specifications
Physical/Environmental:
Models MPSH8-S20-120V, MPSH8-S20-208+V, MPSH8-D20-120V and
MPSH8-D20-208+V:
Width: 19” (48.3 cm) (Including Rack Brackets)
Depth: 8.7” (22.1 cm)
Height: 1.75” (4.5 cm) One Rack U
Models MPSH16-D20-120V, MPSH16-D20-208+V:
Width: 19” (48.3 cm) (Including Rack Brackets)
Depth: 8.7” (22.1 cm)
Height: 3.5” (8.9 cm) Two Rack U
Operating Temperature: 32˚F to 122˚F (0˚C to 50˚C)
Humidity: 10 - 90% RH
Operating Temperature: 32˚F to 122˚F (0˚C to 50˚C)
Humidity: 10 - 90% RH
Network Interface: 10/100Base-T Ethernet, RJ45, multi-session Telnet.
Power Outlets:
MPSH8-S20-120V: Eight (8) each, NEMA 5-15R Outlets.
MPSH8-S20-208+V: Eight (8) each, IEC320-C13 Outlets.
MPSH8-D20-120V: Eight (8) each, NEMA 5-15R Outlets.
MPSH8-D20-208+V: Eight (8) each, IEC320-C13 Outlets.
MPSH16-D20-120V: Sixteen (16) each, NEMA 5-15R Outlets.
MPSH16-D20-208+V: Sixteen (16) each, IEC320-C13 Outlets.
Power Requirements and Maximum Load:
Model No.
Input
Feeds
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
MPSH8-S20-120V 1 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 16 Amps*
MPSH8-S20-208+V 1 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 16 Amps*
MPSH8-D20-120V 2 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 32 Amps*
MPSH8-D20-208+V 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
MPSH16-D20-120V 2 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 32 Amps*
MPSH16-D20-208+V 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
* In accordance with UL requirements, this value has been de-rated to 80%.