Black Box Outlet Managed PDU Multi-tool User Manual


 
OUTLET MANAGED PDU
122
7.7. The Power Cycle Alarm
The Power Cycle Alarm can provide notication when all input power to the Outlet
Managed PDU is lost and then restored. When the power supply is lost and then
restored, the Outlet Managed PDU can provide notication via Email, Syslog
Message or SNMP Trap.
Notes:
• This alarm will not function when only one power input line is
disconnected. To provide notification when one power input line
is lost or disconnected, please use the Lost Voltage (Line In)
Alarm as described in Section 7.4.
• In order for the Outlet Managed PDU to provide alarm notification
via Email, communication parameters must first be defined as
described in Section 5.9.11.
• In order for the Outlet Managed PDU to provide alarm notification
via Syslog Message, Syslog parameters must first be defined and
Syslog Messages must be enabled as described in Section 5.9.2
and Section 11.
• In order for the Outlet Managed PDU to provide alarm notification
via SNMP Trap, SNMP parameters must first be defined, and
SNMP Traps must be enabled as described in Section 5.9.7 and
Section 12.
To congure the Power Cycle Alarm, you must access the Outlet Managed PDU
command mode using a password that permits Administrator Level commands. The
Power Cycle Alarm conguration menu offers the following parameters:
Trigger Enable: Enables/Disables the trigger for this alarm. When
Disabled, this alarm will be suppressed. (Default = On.)
Email Message: Enables/Disables email notication for this alarm.
(Default = On.)
Note:
The Email Message parameter offers four different options: On, Off,
On (Copy to All Triggers) or Off (Copy to All Triggers). If either of
the "Copy to All Triggers" options is selected, then email notification
for all other alarms will be switched On or Off as indicated by this
parameter. For example, If "Off (Copy to All Triggers)" is selected,
then Email notification will be disabled for all other alarms too.