7.8. The Plug Current Alarm
The Plug Current Alarm allows you to monitor current consumption at each of the
Outlet Managed PDU’s switched outlets and generate an alarm when current exceeds
a user-dened "High" threshold or falls below a user-dened "Low" threshold. The
Plug Current Alarm can also be applied to user-dened Plug Groups in order to
generate an alarm when total current consumption for the given Plug Group rises too
high or falls too low.
To congure the Plug Current Alarm, access the Outlet Managed PDU command
mode using a password that permits Administrator Level commands and then use
the Alarm Conguration menu to select the desired alarm feature. The Plug Current
Alarm allows the following parameters to be dened:
Trigger Enable: Enables/Disables the trigger for this alarm. When
Disabled, this alarm will be suppressed. (Default = On.)
Plug Hysteresis: This parameter can be used to prevent the Plug Current
Alarm from generating excessive "Alarm" and "Clear" messages when
current consumption uctuates back and forth across the trigger value.
Basically, the Plug Hysteresis parameter allows you to dene a margin at
both the Low Threshold and High Threshold that the current level must cross
in order to clear an alarm. (Default = 0.5 Amps)
Plug Hysteresis Example: Assume that the Low Threshold for Outlet A1 is
set at 5 Amps, the High Threshold is set at 12 Amps and the Plug Hysteresis
value is set at 1 Amp. When the current goes high or low, the Outlet
Managed PDU will respond as follows:
Low Alarm: If the current drops below 5 Amps, the Outlet Managed PDU
will generate an Alarm. The Alarm will not be cleared until the current
rises above 6 Amps: (5 Amp Low Threshold + 1 Amp Hysteresis Value =
6 Amps.)
High Alarm: If the current rises above 12 Amps, the Outlet Managed PDU
will generate an Alarm. The Alarm will not be cleared until the current
drops below 11 Amps: (12 Amp High Threshold - 1 Amp Hysteresis Value
= 11 Amps.)