Note: Sizes shown are for the conductor do not include any insulation when determining your wire
size.
Figure 40, AWG Wire Size
Table 11, Minimum Recommended Battery Cable Size vs. Cable Length
INVERTER
MODEL
TYPICAL
DC
AMPS
1
NEC
AMPS
2
1 TO 3 FEET
ONE WAY
3 TO 5 FT
ONE WAY
5 TO 10 FT
ONE WAY
SW2512 267 Amps 334 Amps #4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
Not Recommended
SW2612E 278 Amps 348 Amps #4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
Not Recommended
SW3024E or J 160 Amps 201 Amps #4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
SW4024 or W, K 214 Amps 267 Amps #4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
SW3048E or J 80 Amps 100 Amps #2/0 AWG/67.4 mm
2
#2/0 AWG/67.4 mm
2
#4/0 AWG/107 mm
2
SW4048 or K 107 Amps 134 Amps #2/0 AWG/67.4 mm
2
#2/0 AWG/67.4 mm
2
#4/0 AWG/107 mm
2
SW4548E or A 120 Amps 150 Amps #2/0 AWG/67.4 mm
2
#2/0 AWG/67.4 mm
2
#4/0 AWG/107 mm
2
SW5548 147 Amps 184 Amps #4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
#4/0 AWG/107 mm
2
1
TYPICAL DC AMPS is based on Low Battery Voltage with an efficiency of 85%.
2
NEC AMPS is based on Low Battery Voltage, an efficiency of 85%, and a 125% NEC de-rating.
Table 12, Battery Cable to Maximum Breaker/Fuse Size
CABLE SIZE
REQUIRED
RATING IN
CONDUIT
MAXIMUM
BREAKER SIZE
RATING IN
FREE AIR
MAXIMUM
FUSE SIZE
#2 AWG 115 amps 125 amps* 170 amps 175 amps*
#2/0 (00) AWG 175 amps 175 amps 265 amps 300 amps*
#4/0 (0000) AWG 230 amps 250 amps* 360 amps 400 amps*
* The NEC allows rounding up to the next standard fuse size from the cable rating, i.e. 150-amp cable size
rounds up to a standard 175-amp size.
The term "free air" is defined by the NEC as cabling that is not enclosed in conduit or a raceway. Cables
enclosed in raceways or conduits have substantially lower continuous current carrying ability due to
heating factors.
3/0
.475
4/0
.530
250 MCM
.580
300 MCM
.635
350 MCM
.690
400 MCM
.730
500 MCM
.820
1
.335
1/0
.380
2/0
.420
12
.072
10
.115
8
.146
6
.184
4
.235
3
.281
2
.295
14
.073
SIZE
DIAMETE
R
SIZE
DIAMETE
R