Xantrex Technology 120 VAC/60 Portable Generator User Manual


 
TECHNICAL INFORMATION
2001 Xantrex Technology, Inc.
5916 - 195th Street N. E.
Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
SW Series Inverter/Charger
Part No. 2031-5
Rev. C: February 2001
Page
119
SPECIFICATIONS AND FEATURES (50 Hz Models)
Note: All specifications are subject to change without notice.
MODEL SW2612E SW3024E SW3048E SW4548E SW3024J SW4048J SW4548A
General Specifications
Nominal DC Input Voltage 12 Vdc 24 Vdc 48 Vdc 48 Vdc 24 Vdc 48 Vdc 48 Vdc
AC Output Voltage (RMS) 230 Vac 230 Vac 230 Vac 230 Vac 105 Vac 105 Vac 240 Vac
Nominal Frequency 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz
Continuous Power @ 20
°
C
2600 VA 3300 VA 3300 VA 4500 VA 3300 VA 4000 VA 4500 VA
Continuous Output (@ 25
°
C)
11 amps AC 14 amps AC 14 amps AC 20 amps AC 31 amps AC 33 amps AC 20 amps AC
Maximum Output (RMS) 28 amps AC 34 amps AC 34 amps AC 34 amps AC 78 amps AC 78 amps AC 34 amps AC
Efficiency (peak) 90% 94% 95% 96% 94% 95% 96%
Automatic Transfer Relay 30 amps AC 30 amps AC 30 amps AC 30 amps AC 60 amps AC 60 amps AC 30 amps AC
Maximum Charging Rate 150 amps DC 100 amps DC 50 amps DC 60 amps DC 100 amps DC 60 amps DC 60 amps DC
Charger Regulation Method 3 stage 3 stage 3 stage 3 stage 3 stage 3 stage 3 stage
DC Input Requirements
Search Mode 0.08 A (1 W) 0.04 A (1 W) 0.025 A (1 W) 0.04 A (1 W) 0.04 A (1 W) 0.025 A (1 W) 0.04 A (1 W)
On Mode (no load - idle) 1.6 A (12 W) 0.66 A (16W) 0.33 A (16 W) 0.40 A (20 W) 0.40 A (20 W) 0.33 A (16 W) 0.40 A (20 W)
At Full Rated Power 300 amps 166 amps 83 amps 137 amps 137 amps 83 amps 137 amps
Short Circuited Output 700 amps 320 amps 160 amps 180 amps 180 amps 160 amps 180 amps
Input Voltage Range (VDC)
11.8 to 16.5 Vdc
22 to 33 Vdc 44 to 66 Vdc 44 to 66 Vdc 44 to 66 Vdc 44 to 66 Vdc 44 to 66 Vdc
AC Output Characteristics
AC Output Waveform Sine wave, 34 to 52 steps per cycle
Voltage Regulation ± 2%
Total Harmonic Distortion 3 to 5% (stand alone operation)
Power Factor Allowed -1 to 1
Frequency Regulation ± 0.04% (crystal regulated)
Load Sensing Range 16 to 240 Watts
Standard Features
Control Panel Built-in 2 line back-lit alphanumeric liquid crystal display with eight LED status indicators
Low Battery Protection Adjustable low battery cut out and cut in with current compensation
Battery Temperature Sensor 15 foot plug in battery temperature sensor with phone type jack (can be extended)
Auto Generator Control system Automatic generator control system for two and three wire start generators (no glow-plug control)
Auxiliary Relays Three user adjustable voltage controlled signal relays for control of loads or charging sources
Fan Cooling Variable speed brushless DC fans
Options
Remote Control Panel SWRC SWRC SWRC SWRC SWRC SWRC SWRC
Stacking Interface for 2X power
(*requires two inverters)
No No No No No No No
Conduit Box SWCB SWCB SWCB SWCB SWCB SWCB SWCB
Environmental Limitations
Enclosure Type Indoor, ventilated, steel chassis with powdercoat finish
Specified Temp Range
32
°
F to 104
°
F (0
°
C to +40
°
C) (output will meet specified tolerances)
Allowed Temperature Range
-40
°
F to 140
°
F (-40
°
C to +60
°
C) (output may not meet specified tolerances)
Non-operating Temperature
-67
°
F to 284
°
F (-55
°
C to +75
°
C)
Altitude Limit Operating 15,000 feet (5000 meters)
Altitude Limit Non-operating 50,000 feet (16,000 meters)
Dimensions - Inverter Only 15 (38 cm) high, 22.5 (57 cm) wide, 9 (23 cm) deep (when wall mounted)
Dimensions - Shipping 20.5 (52 cm), 27 (69 cm), 15.5 (40 cm)
Mounting Wall or Shelf Mount
Weight - Inverter Only 95 lb (43 kg ) 105 lb (48 kg) 105 lb (48 kg) 136 lb (63 kg) 105 lb (48 kg) 105 lb (48 kg) 136 lb (63 kg)
Weight - Shipping 110 lb (50 kg) 111 lb (50 kg) 111 lb (50 kg) 143 lb (65 kg) 111 lb (50 kg) 111 lb (50 kg) 143 lb (65 kg)