OUTLET MANAGED PDU
44
On - Callback ONLY (With Password Prompt): Callbacks will be
performed for accounts that include a Callback Number, and the username/
password prompt will be displayed when the user’s modem answers (users
will be required to re-enter their username/password when their modem
answers.) Accounts that do not include a Callback Number will not be able
to access command mode via modem.
• Callback Attempts: The number of times that the Outlet Managed PDU will
attempt to contact the Callback number. (Default = 3 attempts.)
• Callback Delay: The amount of time that the Outlet Managed PDU will wait
between Callback attempts. (Default = 30 seconds.)
Notes:
• After configuring and enabling Callback Security, you must then
define a callback phone number for each desired user account
(as described in Section 5.5) in order for this feature to function
properly.
• When using the "On - Callback (With Password Prompt)" option,
it is important to remember that accounts that do not include
a callback number will be allowed to access command mode
without callback verification.
5.3.5. Power Source Conguration
The Power Conguration menu allows you to adjust power measurements in order
to obtain a more accurate determination of how much "real power" is being used by
devices connected to the Outlet Managed PDU. Real Power is determined by the
following equation:
Real Power =
(Voltage * Amps) * Power Factor
Power Efciency
To dene Power Conguration parameters, access the command mode using an
account that permits access to Administrator level commands and then activate the
System Parameters Menu.
Notes:
• In the Text Interface, power source configuration parameters are
defined via the Power Configuration menu.
• In the Web Browser Interface, power source configuration
parameters are selected via the System Parameters menu.