Xantrex Technology Link 1000 Portable Generator User Manual


 
About Link 1000 Settings
33
F10 Select Battery Type
Default: 0 (Liquid Cell)
Range: 0 = Liquid Cell; 1 = Gel Cell (standard); 2 = Gel Cell
(fast charge); 3 = AGM (Absorbed Glass Mat)
This function sets the appropriate charge and float voltages
for the Freedom charger and sets an appropriate Peukert
exponent. Gel cell owners can use Type 1 or Type 2, but
should consult the battery manufacturer before using Type 2.
Type 3 sets Acceptance and Float voltages suited to AGM
type batteries.
F11 Turn on Second Battery Voltage Sense
Default: Off
Range: On, Off
When this function is On, two voltages are displayed. When
the Volts LED is on solid, you see the voltage of the
monitored battery. If the battery Volts LED is flashing,
the second (starting) battery voltage is being displayed.
If you use this function, keep in mind that the displayed
voltage is only an indication of the battery’s state-of-charge if
the battery has been at rest for at least eight hours.
A battery with an eight hour at-rest voltage of 12.4 volts or
more will probably start an engine. A battery with an eight
hour at-rest voltage of 11.1 volts will probably not start an
engine, particularly if you have dirty injectors and if the
engine doesn’t start right away.
F12 Number of Overload Conditions Experienced
Displays the number of inverter shutdowns since the last high
level meter reset. This is primarily a troubleshooting tool.
F13 Number of Inverter Low Battery Shutdowns
Displays the number of inverter low battery shutdowns since
the last high level meter reset. This is primarily a
troubleshooting tool.