Xantrex Technology Link 1000 Portable Generator User Manual


 
About Link 1000 Settings
30
F03 Set or Display Ambient Battery Temperatures
Default: If F16 (Active Temperature Compensation) is On,
the present battery temperature is displayed in °F. If F16 is
Off, the declared battery temperature is displayed.
Range: 30° F–120° F (–1.11° C–48.8° C) in 10° increments.
Set a different value from the default only if the battery
environment is significantly different from 70° F (21.11° C)
when the batteries are being charged by the Freedom
Inverter/Charger.
For more information about battery charging and temperature
compensation, see “F07 Set Temperature Coefficient” on
page 31.
F04 Toggle Display Between Ah and kWhr
Default: Off
Range: Off = Ah display mode; On = kWhr display mode.
When this function is On, the Ah display is changed to a
kilowatt-hour display.
Kilowatt-hours are a very precise measurement of energy
removed from or returned to the battery bank. The Link 1000
uses kilowatt-hours to determine whether 100% of the energy
consumed from the battery has been returned.
A recalculation of the CEF (Charge Efficiency Factor) is not
permitted unless this counter is greater than 0.00 kWhr. This
counter counts down during discharge, and the kWhrs
consumed are displayed with a negative number. While the
battery is charging, the Link 1000 counts back up with 100%
efficiency. CEF recalculation is prevented until a positive
number is in the kWhr counter. This prevents a premature
CEF reset.