24 © 2007 Schneider Electric. All rights reserved.
COM2
Protocol Specifies which protocol is active
ION, Modbus RTU, Modbus
Master
3
, DNP, DLMS,
EtherGate, ModemGate,
GPS: Truetime/Datum
GPS: Arbiter, Factory
ION
Baud Rate
1
Specifies COM port baud rate
during serial communications
300 to 57 600 9 600
Transmit Delay
Specifies the meter’s transmit delay
setting (in seconds)
0 to 1,0 0,010
Unit ID
Identifies the meter during serial
communications
1 to 9 999
From serial
number
2
Serial Port Parity and stop bits for the port 8N1,8N2,8E1,8E2,8O1,8O2 8N1
Port Location
Specifies physical connection point
for COM2
Essailec or Comm Module Essailec
COM3
Protocol Specifies which protocol is active Same as COM2 ION
Baud Rate
1
Specifies COM port baud rate
during serial communications
300 to 115 200 9 600
Transmit Delay
Specifies the meter’s transmit delay
setting (in seconds)
0 to 1,0 0,010
Unit ID
Identifies the meter during serial
communications
1 to 9999
From serial
number
2
Serial Port Parity and stop bits for the port 8N1,8N2,8E1,8E2,8O1,8O2 8N1
RS-232 or RS-485 Specifies RS-232 or RS-485 RS-232, RS-485 RS-232
RTS/CTS
Handshake
Specifies if hardware flow control is
used during RS-232 communication
RTS with delay
RTS/CTS
RTS + delay
COM4
Protocol Specifies which protocol is active
ION, Modbus RTU, DNP,
DLMS, GPS: Truetime/Datum
GPS: Arbiter, Factory
ION
Baud Rate
1
Specifies COM port baud rate
during serial communications
300 to 115 200 9 600
Transmit Delay
Specifies the meter’s transmit delay
setting (in seconds)
0 to 1,0 0,010
Unit ID
Identifies the meter during serial
communications
1 to 9 999
From serial
number
2
Network Setup
IP Address Specifies TCP/IP Ethernet address
000.000.000.000 to
255.255.255.255
None
Mask Specifies Subnet Mask 0.0.0.0 to 255.255.255.0 None
Gateway Specifies Ethernet gateway (if used)
000.000.000.000 to
255.255.255.255
None
SMTP Address Specifies location of SMTP Server
000.000.000.000 to
255.255.255.255
None
Menu Setting Description Range (Values) Default