Schneider Electric ION8800 Weather Radio User Manual


 
© 2007 Schneider Electric. All rights reserved. 23
The following table lists all settings that can be configured via the front panel,
with the meter cover seal in place.
Menu Setting Description Range (Values) Default
Basic Setup
Volts Mode
The power system’s configuration –
WYE, DELTA, etc.
4W-WYE
DELTA
3W-WYE
SINGLE
DEMO
4W-WYE
PT Primary
The Potential Transformer’s primary
winding voltage rating
1 to 999 999 999 120,00
PT Secondary
The Potential Transformer’s
secondary winding voltage rating
1 to 999 999 999 120,00
CT Primary
The Current Transformer’s primary
winding current rating
1 to 999 999 999 5
CT Secondary
The Current Transformer’s
secondary winding current rating
1 to 999 999 999 5
I4 Primary
Primary rating for the I4 current
transformer
1,0 - 999 999,00 5
I4 Secondary
Secondary rating for the I4 current
transformer
1,0 - 999 999,00 5
U1 Polarity
The polarity of the Potential
Transformer on U1
Normal or Inverted Normal
U2 Polarity
The polarity of the Potential
Transformer on U2
Normal or Inverted Normal
U3 Polarity
The polarity of the Potential
Transformer on U3
Normal or Inverted Normal
I1 Polarity
The polarity of the Current
Transformer on I1
Normal or Inverted Normal
I2 Polarity
The polarity of the Current
Transformer on I2
Normal or Inverted Normal
I3 Polarity
The polarity of the Current
Transformer on I3
Normal or Inverted Normal
I4 Polarity
The polarity of the Current
Transformer on I4
Normal or Inverted Normal
Phase Rotation Power system’s phase rotation 123, 132 123
Demand
SWD Subinterval
Intervals used to compute your
Sliding Window Demand values
1 to 5 940 600
SWD #
Subintervals
The number of SWD periods in use 1 to 15 3
SWD Pred Resp 0,00 to 99,00 70
COM1
Protocol Specifies which protocol is active
ION, Modbus RTU, DNP,
DLMS, Factory
ION
Baud Rate
Specifies COM port baud rate
during serial communications
1 200 to 19 200 9 600
Transmit Delay
Specifies the meter’s transmit delay
setting (in seconds)
0 to 1,0 0,010
Unit ID
Identifies the meter during serial
communications
1 to 9 999
From serial
number
2
Serial Port Parity and stop bits for the port 8N1,8N2,8E1,8E2,8O1,8O2 8N1