Environmental Specifications (IEC62052-11)
Installation
DANGER
Do not power up the meter until the ground terminal is connected -- risk of
electric shock.
1. Connect the ground terminal on the rear of the meter to a good earth
ground on the rack, using a 3.3 mm
2
(12 AWG) wire. Ensure that the
terminal nut is tightened down securely onto the ground wire. The wire
must be a minimum of 30 cm long (11.8”) to allow racking and
unracking.
2. Slide the meter into the DIN standard 43862 rack (half-width 19 inch/
482.6 mm rack with plug-in Essailec connector).
3. Ensure the rear connector fits tightly.
4. Tighten the 2 slot-head screws (M3 thread) into the front of the meter rack,
to hold the meter firmly in place.
Mounting Location Indoor use
Metrological -10 to +45ºC (14 to +113ºF)
Operating Range
-25 to +55ºC (-13 to +131ºF)
No formation of ice
Max. Altitude 2000 metres (6562 feet) above sea level
Display Operating Range -10 to +60ºC (14 to +140ºF)
Storage Range -25 to +70ºC (-13 to +158ºF)
Relative Humidity Range 5 to 95% non-condensing
Enclosure Rating IP51 (IEC60529)
Meter Ground
Terminal
465 mm (18.31”)
451 mm (17.76”)
133 mm
(5.24”)
57.1 mm
(2.25”)
37.9 mm
(1.49”)
7 mm
(0.28”)
M6
Cut-out for 482.6 mm (19”)
Chassis
482.6 mm (19”)
Rack
ION8800
Meter
Slot-head
Screws
Meter Essailec
Connector
Rack Essailec
Connector