Schneider Electric ION8800 Weather Radio User Manual


 
© 2007 Schneider Electric. All rights reserved. 21
Ethernet Connections (optional module)
10Base-T
10Base-FL (Fiber)
NOTE
Ethernet connection should be made to either the Fiber port or RJ45 port, not
both, or communications conflicts may result.
Ethernet TCP/IP Service Ports
Internal Modem Connection (COM4 optional module)
Pin 1: Transmit Data +
Pin 2: Transmit Data -
Pin 3: Receive Data -
Pin 6: Receive Data +
Wire Type High quality Category 3 or 5 unshielded twisted pair cable
Connector Type RJ45 modular
Maximum Length 100 m (328 ft)
Type IEEE 802.3 10Base-T for 10 Mbps base band CSMA/CD LANs
Data Rate 10 Mbps
Isolation Transformer isolated to 1500 VAC/2250 VDC RMS
Max. Connections Allowed 4 simultaneous
Wire Type 62.5/125 micrometer multimode fiber optic cable
Connector Type ST
Maximum Length 2000 m (6562 ft)
Data Rate 10 Mbps
Isolation Optical
Protocol Port
ION 7700
Modbus RTU 7701
Modbus TCP 502
EtherGate (COM2) 7802
EtherGate (COM3) 7803
DNP TCP 20,000
ST type fiber cables
Only one EtherGate
connection per port
is allowed at a time
Pin 3: Ring
Pin 4: Tip
Connector Type RJ11
Wire Type Part 68 compliant telephone cord
Data Rate 300 bps – 56 kbps
Error Correction V.42 LAPM, MNP 2-4, V.44
Data Compression V.42 bis/MNP 5