Lincoln Electric SVM192-A Portable Generator User Manual


 
INSTALLATION
A-10 A-10
EAGLE™ 10,000
2
40 Volt
60 Hz.
3-Wire
S
ervice
POWER
COMPANY
METER
240 VOLT
120 VOLT
120 VOLT
L
OAD
N
NEUTRAL
BUS
GROUND
PREMISES
D
ISCONNECT AND
SERVICE
OVERCURRENT
P
ROTECTION
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
240 VOLT
GROUNDED CONDUCTOR
4
0 AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
Connection of EAGLE 10,000 to premises wiring
must be done by a licensed electrician and must
comply with the National Electrical Code and all
other applicable electrical codes.
Figure A.1
CONNECTION OF EAGLE 10,000 TO PREMISES WIRING