Guardian Technologies 4390 Portable Generator User Manual


 
SECTION 3.2
OPERATIONAL ANALYSIS
PART 3
Page 3.2-3
V-TYPE PREPACKAGED
TRANSFER SWITCHES
UTILITY
SOURCE
VOLTAGE
FAILURE
If utility source voltage should drop below a preset value, the generator circuit board will sense the dropout. That
circuit board will then initiate generator cranking and startup after a time delay circuit times out.
Figure 3 is a schematic representation of the transfer switch with generator power available, waiting to transfer.
Generator voltage available E1, E2.
Circuit board action holding Wire 23 open to ground.
Power available to standby coil C2, upon closure of TR, normally open contacts (9 & 6) will close and initiate a
transfer.
Figure 3. Generator Power Available, Waiting to Transfer.