Guardian Technologies 4390 Portable Generator User Manual


 
SECTION 1.6
OPERATING INSTRUCTIONS
7. Set the generator main line circuit breaker to its "On" or
"Closed" position. The generator now powers the
electrical loads.
MANUAL SHUTDOWN AND RETRANSFER
BACK TO "UTILITY"
To shut the generator down and retransfer electrical
loads back to the UTILITY position, proceed as
follows:
1. Set the generator main line circuit breaker to its OFF or
"Open" position.
2. Let the generator run at no-load for a few minutes, to cool.
3. Set the generator AUTO-OFF-MANUAL switch to OFF.
Wait for the engine to come to a complete stop.
4. Turn off the utility power supply to the transfer switch
using whatever means provided (such as a utility source
main line circuit breaker)
5. Manually actuate the prepackaged transfer switch to its
UTILITY source side, i.e., load connected to the utility
source.
6. Turn on the utility power supply to the transfer switch,
using whatever means provided.
7. Set the generator AUTO-OFF-MANUAL switch to
AUTO.
PART 1
GENERAL INFORMATION
Page 1.6-3