Baldor AE11 Portable Generator User Manual


 
4-8 Operation MN2415
Note 1:
Programmable input, can be configured to on of the following:
S Immediate warning close on fault − If the input is activated at any time the unit will alarm and energize the common warning and common alarm output.
S Immediate warning open on fault − If the input is deactivated at any time the unit will alarm and energize the common warning and common alarm output.
S Immediate shutdown close on fault − If the input is activated at any time the generator will be shutdown and energize the common warning and common shutdown output. The
generator can not be started.
S Immediate shutdown open on fault − If the input is deactivated at any time the generator will be shutdown and energize the common warning and common shutdown output.
The generator can not be started.
S Delayed warning close on fault − If the input is activated and the safety time has elapsed the unit will alarm and energize the common warning and common alarm output.
S Delayed warning open on fault − If the input is deactivated and the safety time has elapsed the unit will alarm and energize the common warning and common alarm output.
S Delayed shutdown close on fault − If the input is activated and the safety time has elapsed the generator will be shutdown and energize the common warning and common
shutdown output.
S Delayed shutdown open on fault − If the input is deactivated and the safety time has elapsed the generator will be shutdown and energize the common warning and common
shutdown output.
Table 4-1 Programmable Functions and Values Continued
Auxiliary Output 1
F f f F f f f f
Not Used
yp
F
f
f
F
f
f f F
Pre−heat
f F f
Load Transfer
f F F
Common Warning
F f f
Common Shutdown
F f F
System in Auto
F F f
Common Alarm
F F F
Energize to Stop
See Note 2
Auxiliary Output 2
F f f F F f f f
Not Used
yp
F
f
f
F
F
f f F
Pre−heat
f F f
Load Transfer
f F F
Common Warning
F f f
Common Shutdown
F f F
System in Auto
F F f
Common Alarm
F F F
Energize to Stop
See Note 2
Note 2:
Outputs are solid state, rated at 1.2 Amps and switch to battery negative
when active.
Programmable output can be configured to one of the following:
S Pre−heat. − The output is energized for the period of pre−heat time prior to cranking, and between the cranking attempts.
S Load Transfer. − The output is active after the safety timer has elapsed.
S Common warning. − The output is active if there are any warning alarm active.
S Common shutdown − The output is active if there are any shutdown alarms active.
S System in auto. − The output is active when the system is in automatic mode.
S Common Alarm. − The output is active if there is any alarm condition.
S Energize to stop. − The output is energized when the engine is required to stop (normal or fault conditions), and will remain energized for the period of the Energize To Stop.
Timer, to ensure the engine has come to a complete stop.