Baldor AE11 Portable Generator User Manual


 
4-6 Operation MN2415
Table 4-1 Programmable Functions and Values
Function
!
!!
! 1 !
!!
! 2
Value (Preset in Bold)
PreHeat Timer
f f f f F f f f
0 Seconds
f
f
f
f
F
f f F
5 Seconds
f F f
10 Seconds
f F F
15 Seconds
F f f
20 Seconds
F f F
30 Seconds
F F f
60 Seconds
F F F
180 Seconds
Used to pre−heat the engine prior to cranking. The output is active for the duration of the setting, prior to cranking.
Start Delay
f f f F f f f f
0 Seconds
y
f
f
f
F
f
f f F
5 Seconds
f F f
10 Seconds
f F F
15 Seconds
F f f
20 Seconds
F f F
30 Seconds
F F f
60 Seconds
F F F
180 Seconds
Provides a delay between activating the remote start input, or a mains failure, and actually starting the engine.
Stop Delay
f f f F F f f f
0 Seconds
py
f
f
f
F
F
f f F
5 Seconds
f F f
10 Seconds
f F F
15 Seconds
F f f
20 Seconds
F f F
30 Seconds
F F f
60 Seconds
F F F
180 Seconds
Provides a delay between deactivating the remote start input and actually stopping the engine.
Energize to Stop Hold Timer
f f F f f f f f
0 Seconds
gp
f
f
F
f
f
f f F
5 Seconds
f F f
10 Seconds
f F F
15 Seconds
F f f
20 Seconds
F f F
30 Seconds
F F f
60 Seconds
F F F
180 Seconds
Controls of the engine stop solenoid. When the engine is to be stopped, the Energize To Stop output becomes active, closing the stop solenoid (fuel valve).
When the engine comes to rest, the stop solenoid will remain energized for the period of the Energize To Stop Timer, to ensure the engine has come to a
complete stop.
Warmup Timer
f f F f F f f f
0 Seconds
p
f
f
F
f
F
f f F
5 Seconds
f F f
10 Seconds
f F F
15 Seconds
F f f
20 Seconds
F f F
30 Seconds
F F f
60 Seconds
F F F
180 Seconds
Delay between the engine being available for use, and the closure of the generator load−switching device to allow time for the engine to warm before being
loaded. This occurs after the 12 second safety on timer.