Baldor AE11 Portable Generator User Manual


 
Receiving & Installation 3-9MN2415
General Wiring Considerations
1. Control wires and Power wires cannot be located in the same conduit (NEC Article 725).
2. When routing the interface wiring, do not route it up against anything that could cut or
chafe the wiring. do not route the wire up against any hot or potentially hot object.
3. Make sure that all the electrical components (generator set, transfer switch, battery
charger, etc.) share a common hardwired ground.
4. Check with your local building inspector to determine what you must do to comply with
the local regulations for grounding of this type of permanent installation.
AE8 Electrical Connections Applies only to AE8 Enclosed and Open Series Generators
Single Phase Power Connections
The generator has a 240V single phase AC output. These connections are made at the power
terminal box shown in Figure 3-3.
Figure 3-3 Single Phase Output Power Connections
1
N
AE8 with Enclosure or Open
4
Generator
Output
Customer
AC Output Connections
(to Transfer Switch)
L1
L2
N
L1 to N
L2 to N
L1 to L2
120VAC
120VAC
240VAC
BW0120D
Remote Start and Battery Charger Connections
Figure 3-4 shows the connections for the battery charger and the remote start contacts of the
transfer switch. When the Remote Start Switch is closed, the generator will start. The unit will
remain running until this connection is opened. When the Remote Start Switch is opened, the
control circuits allow the engine to run for approximately 6090 seconds before it shuts off. This
time delay allows the engine to run unloaded to cool down before stopping.
Figure 3-4 Remote Start & Battery Connections
R1
R2
Batt+
Batt−
D1
D2
AE8
with Enclosure
Remote Start Switch
(Close to Start)
Customer Provided Optional Equipment
Twisted Pair Wire
Battery
Charger
Out+
Out−
To 120VAC
(Shore Power)
AE8
Open
Remote Start Switch
(Close to Start)
Customer Provided Optional Equipment
Twisted Pair Wire
Battery
Charger
Out+
Out−
To 120VAC
(Shore Power)
Connect DK1 and DK2 of the battery charger go to the D1 and D2 terminals of the terminal block if a Master Control Systems Inc.
Battery charger is installed. DK1 and DK2 are not polarity sensitive.
Note:
Battery
+−
BW0120D
BW0183D
16AWG
16AWG