Baldor AE11 Portable Generator User Manual


 
Receiving & Installation 3-11MN2415
AE11 Electrical Connections Applies only to AE11 Enclosed Series Generators
Single Phase Power Connections
The generator has a 240V single phase AC output. These connections are made at the power
terminal box shown in Figure 3-7.
Figure 3-7 Single Phase Output Power Connections
L1
L2
AE11 with Enclosure
L3
Generator
Output
Customer
AC Output Connections
(to Transfer Switch)
L1
L2
N
L1 to N
L2 to N
L1 to L2
120VAC
120VAC
240VAC
BW0459D
N
N
G
G
TBP
(Jumpered)
(Jumpered)
Remote Start and Battery Charger Connections
Figure 3-8 shows the connections for the battery charger and the remote start contacts of the
transfer switch. When the Remote Start Switch is closed, the generator will start. The unit will
remain running until this connection is opened. When the Remote Start Switch is opened, the
control circuits allow the engine to run for approximately 6090 seconds before it shuts off. This
time delay allows the engine to run unloaded to cool down before stopping.
Figure 3-8 Remote Start & Battery Connections
TBP
L1
N
G
Remote Start
Fuel Jumper
AE11
with Enclosure
Remote Start Switch
(Close to Start)
Customer Provided Optional Equipment
Twisted Pair Wire
16AWG
BW0459D
Remote Start
Fuel Jumper
Note: Remove Fuel Jumper
if LP Gas is used.
Battery
Charger
Out+
Out−
To 120VAC
(Shore Power)
Battery
+−
Fuel Jumper
IN = Natural Gas
OUT = LPG