A SERVICE OF

logo

86 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Appendix B: Relay Timing
PulseStop Mode
For generators with PulseStop mode starting types (Type 13):
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
If Relay 3 is configured for Preheat, the signal only shows up on Relay 3.
The Preheat on Relay 3 will not overlap the Crank Time if ShutDown
Bypass is not enabled.
If the ShutDown Bypass is enabled, the Preheat on Relay 3 will remain
high for the Crank Time and for the ShutDown Bypass period after
cranking.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3 must
be configured for Preheat with ShutDown Bypass and have the Preheat
time set to zero.
The AGS will make three attempts to stop the generator. If the
generator has still not stopped at the end of the third attempt, the
appropriate Fault will be generated.
Each stop attempt will consist of engaging the stop relay for 5 seconds
and then waiting 20 seconds before checking the state of the Gen Run
Signal to see if the stop attempt was successful.
Figure 41
PulseStop Mode Timing Diagram
Relay 1: Stop
Relay 2: Start (Cranking)
Relay 3: Preheat (Glow)
& Shutdown Bypass
Start
Stop
Preheat
Delay
Crank
Time
Shutdown
Bypass