82 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Appendix B: Relay Timing
RunMode
For generators with RunMode starting types (Types 7, 8, and 14):
Relay 1 (RunStop relay) can be used for two-wire configured
generators.
Relay 1 (RunStop) and Relay 2 (Start) can be used with a common
ground for three-wire configured generators.
The Preheat will never overlap the Crank Time.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Figure 37
RunMode Timing Diagram
Relay 1: Run/Stop
(Ignition)
Relay 2: Start
(Cranking)
Relay 3: Preheat
(Glow)
Start Run Stop
Preheat
Delay
Crank
Time
Shutdown
Bypass