20 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Xanbus Automatic Generator Start Installation
Type 6
Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact.
Figure 12
Type 6 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode GlowStop
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 10 s
Preheat to crank delay 1 s
Crank time 15 s
AGS Harness Wires Generator Wires
18
17
16
15
13
12
14
Relay2
Relay1
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT
STOP
START
For additional information, see “Circuit Limitations” on page 11.
Crank retry time 30 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting