16 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Xanbus Automatic Generator Start Installation
Type 2
Type 2 is a three-wire GlowStop configuration recommended for “three-
wire” generators that don’t require a dedicated preheat signal. In this
configuration, the start signal is applied for longer because the generator
does its own preheat and cranking while the start signal is applied.
Figure 8
Type 2 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode GlowStop
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
18
17
16
14
13
12
Relay1
Relay2
5A fuse
5A fuse
AGSHarnessWires Generator Wires
GENERATOR RUN SIGNAL
START
STOP/PREHEAT
GENERATOR RUN SIGNAL RETURN
For additional information, see “Circuit Limitations” on page 11.
Crank time 30 s
Crank retry time 40 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting