975-0082-01-01 63
Configuration of the Xanbus AGS
User Settings
Use this table to record any customized AGS settings for future reference.
Table 5
Generator Configuration Settings, Values, Defaults,
and User Settings
Setting Values Default
User
Setting
Main Menu Items:
GenMode ManualOn, ManualOff, Automatic ManualOff
Mode Operating/Standby Operating
Configuration Menu Items:
"QT En" Enabled, Off Enabled
"QT Begin" 12:00AM–11:59PM (12-hour
clock)
00:00–23:59 (24-hour clock)
9:00PM (12-hour
clock)
21:00 (24-hour clock)
"QT End" 12:00AM–11:59PM (12-hour
clock)
00:00–23:59 (24-hour clock)
8:00AM (12-hour
clock)
8:00 (24-hour clock)
"Gen Type" Type 1 to Type 14 Type 2
Triggers Menu Items:
"Start DCV 30
sec"
Disabled, 4.0 V–60.0 V 11.3 V
"Start DCV 15
min"
Disabled, 4.0 V–60.0 V Disabled
"Start DCV 2
hr"
Disabled, 4.0 V–60.0 V Disabled
"Start DCV 24
hr"
Disabled, 4.0 V–60.0 V Disabled
"Stop Float" Enabled, Disabled Disabled
"Stop Absorb" Enabled, Disabled Enabled
"Stop V" Disabled, 4.0 V–65.0 V Disabled
"Temp1" Enabled, Disabled Disabled
"Temp2" Enabled, Disabled Disabled
"Load" Enabled, Disabled Disabled
"Start Load" 10.0 A–33.0 A 10.0 A
"Stop Load" 7.0 A–28.0 A 7.0 A
Generator Menu Items:
"Starter Cool
Down"
1s to 250s (increments of 1s) 60s
"Gen Cool Down" 0s to 90 s (increments of 1s) 30s
"Gen Spin Down" 0s to 900s (increments of 1s) 3s
"Max Run Time" 0hours–24 hours 8hours
"Exercise Per" 0days (Off)–250days 21days
"Exercise Dur" 1min–250min 30min
"Exercise Time" 12:00AM–11:59PM (12-hour
clock)
00:00–23:59 (24-hour clock)
9:00AM (12-hour
clock)
9:00 (24-hour clock)
"Relay3" Preheat, WrmupCoolDn, Preheat
SDByp, NotUsed
NotUsed
"Gen Run Hold
Time"
0.5s to 20s (increments of 1s) 0.5s
"Crank Delay" 0s to 60s (increments of 1s) 0s
"Crank Time" 0s to 250s (increments of 1s) 30s
"Crank Retry
Time"
0s to 250s (increments of 1s) 40s
"Preheat Time" 0s to 250s (increments of 1s) 0s
"Gen Start
Tries"
1 to 10 3
Table 5
Generator Configuration Settings, Values, Defaults,
and User Settings
Setting Values Default
User
Setting