A SERVICE OF

logo

24 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Xanbus Automatic Generator Start Installation
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.
Figure 18
Type 10 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode StartStop
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
Crank time 15 s
Crank retry time 30 s
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
STOP
START
AGS Harness Wires Generator Wires
For additional information, see “Circuit Limitations” on page 11.
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting