6. Before proceeding, check that the cable polarity is correct: POSITIVE (+) on
the inverter/charger is connected to the POSITIVE (+) on the battery, and
NEGATIVE () cable is connected to the NEGATIVE () terminal on the
inverter/charger.
7. Connect the other end of the NEGATIVE () cable to the NEGATIVE ()
terminal on the battery.
8. Use a wrench to tighten the bolt to a torque of 1516 ft-lbs (20.421.7 Nm
) at
the inverter/charger end.
9. Attach the DC terminal covers using the screws provided to protect the DC
terminals, as shown in Figure 8.
Figure 7
DC Cable Connections
Important:
The next step is the last cable connection you need to make. A spark is
normal when this connection is made.
Figure 8
DC Terminal Covers