NETWORK SETUP
IP ADDRESS Sets the IP address for the meter
000.000.000.000 to
999.999.999.999
varies
3
SUBNET MASK
Used if subnetting applies to your
network
000.000.000.000 to
999.999.999.999
255.240.0.0
GATEWAY
Used in multiple network
configurations
000.000.000.000 to
999.999.999.999
0.0.0.0
DNS PRIMARY
Sets the address for the primary
DNS Server that is configured to
resolve domain names
000.000.000.000 to
999.999.999.999
none
DNS
SECONDARY
Sets the address for the secondary
DNS Server that is configured to
resolve domain names
000.000.000.000 to
999.999.999.999
none
10/100BT
CONFIG
Sets the BASE-T Ethernet max. link
speed and duplexing
Auto, 10BT half, 10BT full,
100BTX half, 100BTX full
Auto
100BFX CONFIG Sets the Fiber Ethernet duplexing Full Duplex or Half Duplex Full Duplex
SNMP SERVER
Determines whether SNMP protocol
is enabled on the meter or not
Enabled or Disabled Disabled
PQ SETUP
SWELL LIMIT
Specifies the magnitude above
which an input must rise for a swell
to be recorded
100 to 1000 106
SAG LIMIT
Specifies the magnitude below
which an input must fall for a sag to
be recorded
0 to 100 88
CHANGE
CRITERIA
Specifies the amount by which an
input must change during a
disturbance to be considered a new
sub-disturbance
0 to 100 10
NOMINAL
VOLTAGE
4
Specifies the nominal voltage of the
power system
0 to 1,000,000 0
EVENT PRIORITY
Assigns a priority level to sag/swell
events
0 to 255 200
FORMAT SETUP
DIGIT GROUP
Specifies symbols used to delimit
thousands & decimal place holder
1000.0 or 1,000.0 or 1000,0 1000.0
VOLTS DECIMAL
Number of decimal places
displayed for voltages
1. to 123456789.XXX 1.XX
CURRNT
DECIMAL
Number of decimal places
displayed for currents
1. to 123456789.XXX 1.XXX
POWER DECIMAL
Number of decimal places
displayed for power measurements
1. to 123456789.XXX 1.XXX
MEAS SYMBOL
Specifies the convention used for
displaying measurements
IEEE or IEC IEEE
PHASE LABEL Specifies how phases are labelled ABC, RST, XYZ, RYB, RWB, 123 ABC
PF SIGN
Specifies the power factor sign
convention used
IEEE or IEC IEEE
PF SYMBOL
Sets how power factor is labelled
(LD = leading/LG = lagging)
LD/LG, +/-, CAP/IND LD/LG
DATE FORMAT Specifies how dates are displayed
MM/DD/YYYY, DD/MM/YYYY,
YYYY/MM/DD
MM/DD/
YYYY
TIME FORMAT
Specifies whether time is displayed
in 12 hour or 24 hour clock format
12 H or 24 H 24 H
DISPLAY DST
Specifies whether or not DST is
displayed
Yes or No Yes
Menu Setting Description Range (Values) Default