© 2007 Schneider Electric. All rights reserved. 21
COM1 SETUP
PROTOCOL The communications protocol
ION, Modbus RTU, Modbus
Master, DNP V3.00,
GPS:Truetime/Datum,GPS:
Arbiter, GPS:Arbiter-Vorne,
Factory, Ethergate, ModemGate
ION
BAUD RATE The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
19,200
TRAN DELAY The transmit delay in seconds 0 to 1 0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number
1 to 9999
From serial
number
2
SERIAL PORT Parity and stop bits for the port 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1
MODE Hardware mode for the port RS232 or RS485 RS232
FLOW CONTROL
Specifies the handshake mode
when COM1 is set to RS232
RTS + DELAY or RTS/CTS
RTS +
DELAY
RS485 BIAS
Turns on biasing when Mastering
on the RS-485 bus
ON or OFF OFF
COM2 SETUP
PROTOCOL The communications protocol See COM1 protocol ION
BAUD RATE The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
19,200
TRAN DELAY The transmit delay in seconds 0 to 1 0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number
1 to 9999 101
SERIAL PORT Parity and stop bits for the port 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1
RS485 BIAS
Turns on biasing when Mastering
on the RS-485 bus
ON or OFF OFF
COM3 SETUP
PROTOCOL The communications protocol
ION, Modbus RTU, Modbus
Master, DNP V3.00,
GPS:Truetime/Datum,GPS:
Arbiter, GPS:Arbiter-Vorne,
Factory
ION
BAUD RATE The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
19,200
TRAN DELAY The transmit delay in seconds 0 to 1 0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number
1 to 9999 102
ANSWER HR
RINGS
The number of rings during defined
answer hours
0 to 255 1
NON-ANSWER
HR RINGS
The number of rings during defined
non-answer hours
0 to 255 5
COM4 SETUP
PROTOCOL The communications protocol
ION, Modbus RTU, DNP V3.00,
Factory
ION
BAUD RATE The data rate, in bits per second
1200, 2400, 4800, 9600,
19200
9600
TRAN DELAY The transmit delay in seconds 0 to 1 0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number
1 to 9999 103
SERIAL PORT Parity and stop bits for the port 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1
Menu Setting Description Range (Values) Default