Front Panel Setup Menu Settings
The following table lists all settings that can be configured via the front panel.
Menu Setting Description Range (Values) Default
BASIC SETUP
VOLTS MODE
The power system’s configuration –
WYE, DELTA, etc.
4W-WYE, DELTA, 3W-WYE,
SINGLE, DEMO
4W-WYE
PT PRIMARY
The Potential Transformer’s primary
winding voltage rating
1 to 999,999.99 120.00
PT SECONDARY
The Potential Transformer’s
secondary winding voltage rating
1 to 999,999.99 120.00
CT PRIMARY
The Current Transformer’s primary
winding current rating
1 to 999,999.99 5.00
CT SECONDARY
The Current Transformer’s
secondary winding current rating
1 to 999,999.99 5.00
V4 PRIMARY
The Potential Transformer’s primary
winding voltage rating on V4
1 to 999,999.99 120.00
V4 SECONDARY
The Potential Transformer’s
secondary winding voltage rating
on V4
1 to 999,999.99 120.00
I4 PRIMARY
The Current Transformer’s primary
winding current rating on I4
1 to 999,999.99 5.00
I4 SECONDARY
The Current Transformer’s
secondary winding current rating
on I4
1 to 999,999.99 5.00
I5 PRIMARY
The Current Transformer’s primary
winding current rating on I5
1 to 999,999.99 5.00
I5 SECONDARY
The Current Transformer’s
secondary winding current rating
on I5
1 to 999,999.99 5.00
V NOMINAL
The V1, V2 and V3 nominal voltage
used for harmonics calculations
1.000 to 999,999.000 120.00
V4 NOMINAL
The V4 nominal voltage used for
harmonics calculations
1.000 to 999,999.000 120.00
Va POLARITY
The polarity of the Potential
Transformer on Va
Normal or Inverted Normal
Vb POLARITY
The polarity of the Potential
Transformer on Vb
Normal or Inverted Normal
Vc POLARITY
The polarity of the Potential
Transformer on Vc
Normal or Inverted Normal
V4 POLARITY
The polarity of the Potential
Transformer on V4
Normal or Inverted Normal
Ia POLARITY
The polarity of the Current
Transformer on Ia
Normal or Inverted Normal
Ib POLARITY
The polarity of the Current
Transformer on Ib
Normal or Inverted Normal
Ic POLARITY
The polarity of the Current
Transformer on Ic
Normal or Inverted Normal
I4 POLARITY
The polarity of the Current
Transformer on I4
Normal or Inverted Normal
I5 POLARITY
The polarity of the Current
Transformer on I5
Normal or Inverted Normal
CURRENT PROBE
TYPE
The type of current probes being
used with the meter
Factory Default, User Defined 1,
or User Defined 2
Factory
Default