Mitsubishi Electronics 9700 Series Portable Generator User Manual


 
MITSUBISHI
ELECTRIC
9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3
-1
MITSUBISHI ELECTRIC 9700 SERIES UPS
3.0 INSTALLATION AND OPERATION
3.1 Transportation and Installation
TABLE 3.1 How to transport and install the system
Transportation Installation
Transport unit with forklift.
Use eye bolts (supplied) to carry with
overhead crane.
Using the holes (4 - 24) pre drilled into the
UPS channel base, anchor the unit using
appropriate hardware.
Note :
Do not transport in a horizontal position. Cabinets should be maintained
upright within +/- 15° during handling
.
3.2 Installation Procedure
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of weights of UPSs.
TABLE 3.2 List of UPS weights
UPS Capacity (kVA) 100 150 225 300 375
Weight (lb.) 3060 3810 4960 5890 6620
B) Minimum clearance required for ventilation
Right side
1.0" (25 mm) (not required when sidecars are used)
Left side
1.0" (25 mm) (not required when sidecars are used)
Back side
0.0" (0.0 mm)
Top side
23.6" (600 mm) (for air flow)
C) Space requirement for routine maintenance
Allow the following space at the time of installation.
Front
39.4" (1000 mm)
Sides
0.0" (0.0 mm)
Rear
0.0" (0.0 mm)