MITSUBISHI ELECTRIC 9700 SERIES UPS
1.3 Specifications
The UPS name plate displays the rated kVA as well as nominal voltages and
currents. The name plate is located on the interior side of the UPS front door.
TABLE 1.1 Power Specifications
Rated output
Power
Input voltage
3 Φ / 3 wire
Output voltage
3 Φ /3 or 4 wire
100kVA / 80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
208V, 480V or 600V
208V, 480V or 600V
208V, 480V or 600V
208V, 480V or 600V
208V, 480V or 600V
208V, 480V or 600V
208V, 480V or 600V
208V, 480V or 600V
480V or 600V
480V or 600V
TABLE 1.2 UPS Module Information
UPS
[kVA]
CABLE
ENTRY
WIDTH
[in / mm]
DEPTH
[in / mm]
HEIGHT
[in / mm]
WEIGHT
[lb./ kg]
HEATING
[kBTU/h]
100 BOTTOM 35.4 / 900 29.9 / 759 79.7 / 2025 1900 / 860 31.0
150 BOTTOM 47.2 / 1200 29.9 / 759 79.7 / 2025 2350 / 1065 45.3
225 BOTTOM 55.1 / 1400 29.9 / 759 79.7 / 2025 3300 / 1495 63.0
300 TOP 94.5 / 2400 38.3 / 974 79.7 / 2025 4950 / 2240 113.8
375 TOP 94.5 / 2400 38.3 / 974 79.7 / 2025 5550 / 2515 149.4
TABLE 1.3 Input Cabinet Information
UPS
[kVA]
INPUT
VOLTAGE[V]
CABLE
ENTRY
WIDTH
[in / mm]
DEPTH
[in / mm]
HEIGHT
[in / mm]
WEIGHT
[lb./ kg]
100 480 TOP 36.0 / 910 29.9 / 759 79.7 / 2025 1275 / 580
150 480 TOP 44.0 / 1118 29.9 / 759 79.7 / 2025 1325 / 600
225 480 TOP 44.0 / 1118 29.9 / 759 79.7 / 2025 2000 / 910
300 480 TOP 44.0 / 1176 38.3 / 973 79.7 / 2025 2600 / 1180
375 480 TOP 54.0 / 1320 38.3 / 973 79.7 / 2025 3000 / 1360