TABLE 1.5 Rating of Circuit Breakers (MCCB) and Fuses
NUMBER APPLICATION OUTPUT CAPACITY OF EQUIPMENT
100kVA 150kVA 225kVA 300kVA 375kVA
208V 480V 600V 208V 480V 600V 208V 480V 600V 480V 600V 480V 600V
M CB1 AC input circuit breaker - --------600A400A800A600A
C
52RC AC input contactor 350A 420A 660A - -
C
CB2
Battery disconnect circuit
breaker
400A 600A 800A 1200A 1600A
B
CB101 Control circuit breaker 15A 30A
F
FCU, FCV, FCW,
FCX, FCY, FCZ
Converter main circuit fuse 450A 630A 900A 900A 800A
U
FIU, FIV, FIW,
FIX, FIY, FIZ
Inverter main circuit fuse 450A 630A 900A 900A 800A
(OPTION)
FSU, FSV, FSW
Bypass main circuit fuse 450A - 630A - 900A - - -
S
FUD1, 2 Control power fuse DC500V 3A DC500V 3A DC500V 3A DC500V 3A DC500V 3A
E
FUS1, 2, 3 Bypass input ZNR fuse AC600V 10A AC600V 10A AC600V 10A AC600V 10A AC600V 10A
S
FZS1, 2, 3 Bypass input ZNR fuse AC600V 30A AC600V 30A AC600V 30A AC600V 30A AC600V 30A
FBS1, 2 CB3 control circuit fuse AC600V 5A AC600V 5A AC600V 5A AC600V 5A AC600V 5A
FZC1, 2, 3 AC input ZNR fuse AC600V 30A AC600V 30A AC600V 30A AC600V 30A AC600V 30A