Lochinvar 502 - 2072 Patio Heater User Manual


 
1 Service
8
General Operation
How the appliance operates
The Copper-fin uses a finned copper tube heat exchanger to
transfer heat from the flue products to the water. An electronic
control module monitors various inputs to initiate a call for
heat. The blower provides both primary and secondary air to
the burner and forces the flue products out of the combustion
chamber and into the vent system. The control module
regulates the blower speed (on B9 and M9 models) to control
the firing rate of the appliance. The modulating gas valve
monitors the amount of combustion air being pulled into the
blower and regulates the amount of gas supplied, which then
mixes with the combustion air and is supplied to the burner.
How the control module operates
The Copper-fin control module receives input from appliance
sensors. The control module activates and controls the
blower and gas valves to regulate heat input and switches
heater, DHW and system pumps on and off as needed. The
user/installer programs the module to meet system needs by
adjusting control parameters. These parameters set operating
temperatures and heater operating modes. Appliance operation
can be based on heater outlet water temperature, heater return
water temperature, system supply temperature, system return
temperature or tank temperature, depending on the parameter
setting.
Sequence of operation
Table 1A shows control module normal sequences of operation
for space heating and DHW operation. The combined operation
sequence is for a typical application, programmed to provide
DHW priority.
Access modes
User
The user can adjust space heating set point using the UP
and DOWN buttons at any time during normal operation.
By entering the USER code (0704), the user can also change
temperature units, time and date, and night setback settings.
In user mode, the following parameters can be viewed but not
changed: Heater outlet water temperature in DHW mode;
heater model number; software version; total operating hours,
and total cycles.
Installer
Most parameters are available only to the installer, accessible
only by entering the installer access code (5309).
Saving parameters
To save parameters and exit programming:
Press the ENTER/RESET button, then the MENU/EXIT button
3 times.
To keep parameter settings only for a current operating cycle:
Press the MENU/EXIT button 3 times after making all desired
parameter changes.
To enter a parameter and continue programming:
Press the MENU/EXIT button 1 time to return to the parameter
listings; press again to return to the menu listings. Remember
to press the ENTER/RESET button when finished programming
in order to save the changes made.
Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual