Lochinvar 502 - 2072 Patio Heater User Manual


 
3 Troubleshooting
40
FAULT DESCRIPTION CORRECTIVE ACTION
Temp O/Shoot
(Lockout will reset
automatically after 5
minutes or may be
reset immediately once
condition has been
corrected. Press the
RESET button on the
SMART SYSTEM display
to reset.)
The temperature rise across the heat
exchanger has exceeded the set parameters
for the appliance.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the appliance is piped properly into the
heating system. Refer to the Water Connections
Section of the Installation and Operation Manual for the
proper piping methods.
• Check for 120 VAC to the pump motor on a call
for heat. If voltage is not present, check the wiring
leading to the main control board. Replace the main
control board if necessary.
• If 120 VAC is present on a call for heat and the
pump is not operating, replace the pump.
Outlet water temperature has exceeded the
maximum outlet water temperature.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the appliance is piped properly into the
system. Refer to the Water Connections Section of
the Installation and Operation Manual for the proper
piping methods.
• Check 120 VAC to the pump motor on a call for heat.
If voltage is not present, check wiring leading to the
main control board. Replace the main control board
if necessary.
• If 120 VAC is present on a call for heat and the
pump
is not operating, replace pump.
• Replace the main control board.
Rem Ctrl Flt
External control is cycling too often. • Check set point of the external control.
• Check the wiring between the external control and
the unit.
• Replace the control.
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface
Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual