Lochinvar 502 - 2072 Patio Heater User Manual


 
3 Troubleshooting
32
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.
• Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON position.
• Check 120 VAC through the ON/OFF switch. No
voltage through switch, replace switch.
- Bad wiring connection.
• Check wiring harness connection between the display
board and the main control board. Connect the harness
at both points.
- Blown fuse.
• Replace fuse F6 on the main control board, see
FIG. 3-1 on page 31 of this manual.
- Bad display board. • Replace board.
- Bad main control board. • Replace main control board.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat satisfied.
• Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) set point for
main control board.
Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3D on page 33 of this manual.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on pages 35 - 42 of this manual for
corrective actions.
Unit Does Not
Modulate to
100%
- Ramp delay active.
• Check ramp delay parameter settings. Optional PC
software required.
• Turn ramp delay feature off. See page 18 of this
manual for instructions on how to turn this feature off.
- Boiler controlled by BMS.
Check BMS parameter settings. Optional PC
software required.
- Outlet temperature too high.
- Delta T too high.
Table 3A Troubleshooting Chart - No Display
Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual