W203 Manual Off: Max
generator run time
reached. Reset
GenMode.
No The generator has run for
its maximum allowable
time. The XW Auto
Generator Start has stopped
the generator and changed
the GenMode to
[ManualOff].
Acknowledge the warning.
Return the XW Auto
Generator Start to the
desired GenMode
[Automatic or ManualOn].
Ensure generator has fuel
and is supplying the
required power for battery
charging and loads.
W205 Generator started
by its switch. Use
its switch to stop.
Yes The generator was started,
but not by the XW Auto
Generator Start.
Check your generator. Stop
it using the switch or
control panel on the
generator.
W206 Mismatched
triggers. Enable
stop trigger or
disable start trigger.
No You have set a start trigger,
but not a corresponding
stop trigger.
Acknowledge warning and
set a stop trigger.
W207 Mismatched
triggers. Enable
start trigger or
disable stop trigger.
No You have set a stop trigger,
but not a corresponding
start trigger.
Acknowledge warning and
set a start trigger.
W208 Automatic start and
stop triggers not
enabled. Configure
triggers.
No You are attempting to enter
Automatic Mode without
setting triggers.
Acknowledge warning and
set start and stop triggers.
W209 Gen external stop.
Start gen via its
control panel.
Yes The generator has stopped,
but not by the XW Auto
Generator Start. The
generator may have run out
of gas, or may have been
shut off by a switch on the
generator.
Check the generator’s fuel
level and mechanical
condition, then start the
generator manually (using
the switch or control panel
on the generator) to clear
the warning.
Table 5-1
XW Auto Generator Start Warning Messages(Continued)
Warning
Number Message
Self-
clearing? Cause Action