Xantrex Technology XW Portable Generator User Manual


 
Configuration
3–10 975-0307-01-01
When to use Use this setting after installing the XW Auto Generator Start hardware.
Selecting a suitable “Gen Type” automatically configures the XW Auto
Generator Start to work with the ignition system and starting
requirements of the generator. Consult the generator manual or contact
the generator’s manufacturer for specific generator starting requirements.
Outcomes Selecting a “Gen Type” from the list automatically configures the
following settings:
Preheat time
Preheat end to crank delay time
Crank time
Crank retry time
Starter Cool Down time
Generator Cool Down
Generator Run Signal hold time
Start tries.
If the presets will not work with the desired generator, it may be necessary
to manually configure some of the settings listed above using information
from the generator manufacturer. These settings can be changed in the
CfgGen Menu on page 3–20.
Type 6 GlowStop with normally closed
RunStop contact
page 2–14 Yamaha
Type 7 Run with preheat page 2–15 Generac Backup/Renewable
Type 8 Run with no preheat page 2–16 Northern Lights and Fisher Panda
Type 9 StartStop with Relay 3 preheat and
shutdown bypass
page 2–17 Westerbeke
Type 10 StartStop page 2–18 Generac
Type 11 MomentaryRun page 2–19 Kohler
Type 12 GlowStop with no preheat page 2–20 Onan Propane
Type 13 PulseStop with Relay 3 preheat page 2–21 PowerTech Diesel
a.See Appendix C, “Relay Timing” for additional information.
b.Examples of generators are suggestions only and do not imply that those generators must be
used with the associated generator types.
Table 3-1
Generator Type Descriptions and Examples(Continued)
Option
Description
Mode
For Technical
Details, see...
a
Examples of Generators
b